Customization: | Available |
---|---|
Warranty: | 1year |
Output Type: | AC Three Phase |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Gas generator data | |
Genset model | U1GC1000-G |
Continuous power (kW/kVA) | 1000/1250 |
Connection type | 3 phases 4 wires |
Power factor | 0.8 lagging |
Voltage | 10.5kV |
Frequency (Hz) | 50 |
Gas genset electrical efficiency | 38% |
Gas genset thermal efficiency | 45% |
Total efficiency | 83% |
Gas consumption at full load | 9.47MJ/kWh |
Lubricant oil consumption | 0.36g/kWh |
Voltage Stabilized regulation | ≤±1.5% |
Voltage Instantaneous regulation | ≤±20% |
Voltage Recovery time (s) | ≤1 |
Voltage Fluctuation ratio | ≤1% |
Voltage Wave aberration ratio | ≤5% |
Frequency Stabilized regulation | ≤1%(adjustable) |
Frequency Instantaneous regulation | -10%~12% |
Frequency Fluctuation ratio | ≤1% |
Net weight(kg) | 13,980 |
Containerized type dimension(mm) | 12.192×2.438×2.896 |
UK Deepsea controller DSE8620 MKII(Or ComAp controller IG500-G2) |
|
Synchronization/Parallel Panel | |
Model | U1S1000 |
Capacity | 2000A |
Air circuit breaker brand | CHINT |
Controller | DSE8620 MKII /ComAp IG500G2 |
Features:
|
40ft high containerized canopy |
Features:
3. Weather-proof, dust-proof, sound-proof, suitable for rigorous environment. 4. All canopy parts are designed with modular principles and canopy materials use strong steel board. 5. All metal canopy parts are painted by electrostatic polyester powder paint. 6. Efficient air intake and exhaust system to ensure stable output. 7. Scientific design and advanced techniques to reduce noise level to 75-85db(A), materials and its covers further ensure sound-absorbing efficiency and protection function. 8. Locks of canopy design are more convenient for the operation and maintenance also ensure the safety of gen-set more. 9. Lifting-eye and forklift design are easy for transportation. 10. Emergency stop push button outside of canopy. 11. Well-formed and compact design, the big built-in muffler makes the noise lower. |
Automatic Oil filling, KENCO brand |
Features: Automatically add lubricant oil for gas gen-set |
Horizontal remote radiator |
Standby remote radiator will run to cool engine when: 1. The heat recovery system is not working due to maintenance/repair. 2. Customer does not need hot water, but need gas genset to run to produce electricity only. 3. Engine coolant temperature is too high. |
Heat recovery system(OPTIONAL) | |
Material | Stainless steel |
Heat exchangers | Jacket water plate heat exchanger and exhaust heat exchanger |
Electrical efficiency | 38% at 1000kWel |
Thermal efficiency | 45% |
Thermal power | 1184kWth |
Inlet water temperature | 60ºC |
Outlet water temperature | 85ºC |
Hot water flow rate | 11.3L/s |
Features: Increase the total efficiency. Hot water can be for the life and industrial use |
Items | Quantity |
Silencers | 2 |
Elbows | 1 set |
Screws and flanges | 1set |
Asbestos Pad | 1 set |
Anti-rust liquid | 1 |
Genset starting free maintenance batteries, Battery charger, Battery cables | 1 set |
Standard toolbox | 1 |
Documents list: | |
Gen-set operation manual, Genset maintenance manual | 1 set |
Engine part book | 1 |
Alternator manuals, maintenance manuals, parts book | 1 set |
Genset installation drawings electrical system drawings. | 1 set |
ComAp IG-NT Controller instruction | 1 |
Engine Certificate, Alternator Certificate, Gen-set Certificate | 1 |
Gen-set Testing Reports | 1 |